Salicru SLC CUBE 3+ PS Mode D'emploi page 126

Publicité

Les langues disponibles

Les langues disponibles

... where AAAAAA corresponds to the language of the menus
displayed in the LCD panel. The available languages are: Eng-
lish, Spanish, French, German, Turkish and Russian.
By means of the keys () and (), move till selecting the
language and validate with (ENT). Since this moment, the
screens will be displayed in the set language (in this case Eng-
lish).
The screen to set the time (hour, minutes, seconds) and date
(day of the week, day of the month, month and year) will be
displayed.
Clock: HH:MM:SS
Date: WKD DD/MM/YYYY
To begin the time and date setting press (ENT). Each character
that has a value, it is modified one by one, to change the first
character of the field use the keys () and () and validate
with (ENT). To jump to the next character use the keys ()
and (). To finish press (ESC), the values will be validated and
the following screen is displayed.
UNIT NOMINAL VOLTAGE
... where AAA corresponds to the nominal phase to phase
value, of the operating voltage of the equipment.
By means of the keys () and (), move it till the nominal
ˆ
value of the power supply voltage and validate it with
(ENT).
When the wished value is not in the chart 4, select the
closest one and validate with (ENT).
Type of voltage interval
LV (Low voltage),
Referred to the model
HV (High voltage)
Tab. 4. Nominal values, operating voltages of the equipment.
Once the operating voltage is selected, it is compulsory to
select the nominal frequency. The following message is dis-
played:
NOMINAL FREQUENCY
By means of the keys () and (), move till one of the
ˆ
following frequency values and validate with (ENT):
50 Hz: Frequency of the equipment (rectifier and in-
verter), will be set to 50 Hz.
60 Hz: Frequency of the unit (rectifier and inverter), will
be set to 60 Hz.
126
LANGUAGE
AAAAAA
3 X AAA V
Value of phase to phase
voltage
3x200 V / 3x208 V / 3x220 V /
3x230V
3x380 V / 3x400 V / 3x415 V
AAAA
AUTO: In each UPS start up, the input frequency will
be sensed and set to 50 or 60 Hz accordingly.
This setting is not recommended if the unit is sup-
plied by a generator set.
Once the working frequency has been selected, and only for
LV equipment (low voltage, "A" in the model reference),
it is possible to choose the number of batteries, among the fol-
lowing options: 36 (18+18), 38 (19+19) y 40 (20+20). Choose the
correct value using the keys () and (), and confirm with
(ENT).
BATTERY NUMBER
36 (18+18)
This configuration is indicated on the equipment label, or bat-
tery cabinet, see Fig. 39.
In HV (high voltage) equipment, the number of batteries is
fixed, 62 (31+31) and, therefore, this configuration screen does
not appear.
The next adjustment to make is the number of battery strings.
STRINGS NUMBER
1
On the battery configuration label (see Fig. 39), the number of
battery strings (between 1 and 6) is also indicated. Enter this
value in this configuration screen (modification using the keys
() and (), and confirm with (ENT)).
As the last battery configuration data, we must enter the ca-
pacity of each of the battery blocks that make up the string(s)
(between 3.0Ah and 900.0Ah). Obtain the value to enter ac-
cording to the label (see Fig. 39). Scroll through the digits with
keys () and (), modification with keys () and (), and
confirm with (ENT).
SINGLE BATT. BLOCK
CAPACITY: xxx.xAh
Once the capacity of the battery blocks has been selected,
choose the parameters that configure the "Peak Shaving"
mode. First, set the input power limit (PEAK SHAVING
parameter in kW), scroll through the digits with the () and
() keys, modify with the () and () keys, and confirm
and jump to the next parameter with (ENT). Next, choose
whether the static bypass will be enabled in case of equipment
stoppage (by alarm or manually). Using the () and () keys
it is possible to select "YES" or "NO", and confirm with (ENT).
Pressing
(ENT)
returns you back to the first parameter on this
screen. If everything is correct, press
screen.
PEAK SHAVING: xxx kW
BYPASS ENABLED? <YES/NO>
Once the "Peak Shaving" parameters have been selected, the
following message will appear:
CONFIG. COMPLETED ?
<ENT> YES <ESC> NO
(ESC)
to jump to the next