PARAMETERS
screen 3.0
By pressing (ESC) key from any screen of any submenu, it is gone
back to main screen (Screen 0.0).
Fig. 52. Screen 3.0 «Parameters» and its submenus.
Screen 3.3: This screen allows setting the BAUD RATE of
•
communication port #0. Options:
"1200"
"2400"
"4800"
"9600"
"19200"
Screen 3.4: This screen allows setting the PARITY type of
•
communication port #0. Options:
"NONE"
"ODD"
"EVEN"
Screen 3.5: This screen allows setting the number of STOP
•
BITS of communication port #0. Options:
"1"
"2"
Screen 3.6: This screen allows setting the protocol type of
•
communication port #0. Options:
"SEC"
"MODBUS"
Screen 3.15: This screen allows setting the frequency of the
•
automatic battery test. Options:
"DISABLED": The automatic battery test is disabled.
"WEEKLY": The automatic battery test runs once per
week.
"MONTHLY": The automatic battery test runs once per
month.
"YEARLY": The automatic battery test runs once per year.
Screen 3.16: Weekday when the battery test is done. Op-
•
tions:
"MON": For Monday.
"TUE": For Tuesday.
142
()
Clock: 11:19:35
()
Date: 11/09/2013
screen 3.1
()
Port 0 Parity
()
NONE
screen 3.4
()
Autom. Battery Test
()
Type: DISABLED
screen 3.15
()
Autom. Battery Test
()
Day/Month: 1/JAN
screen 3.18
()
Language : English
()
Modbus Address : 1
screen 3.2
()
Port 0 Stop Bits
()
1 Bit/s
screen 3.5
()
Autom. Battery Test
()
Week day : MON
screen 3.16
Bypass Enabled? YES
()
()
screen 3.19
"WED": For Wednesday.
"THU": For Thursday.
"FRI": For Friday.
"SAT": For Saturday.
"SUN": For Sunday.
Screen 3.17: This screen allows setting the time "hh:mm"
•
(hours/minutes) in 24h format of the automatic battery test.
Screen 3.18: This screen allows setting the day from 1 to 31
•
and the month of the automatic battery test according to one.
Options:
"JAN": For January.
"FEB": For February.
"MAR": For March.
"APR": For April.
"MAY": For May.
"JUN": For June.
"JUL": For July.
"AUG": For August.
"SEP": For September.
"OCT": For October.
"NOV": For November.
"DEC": For December.
Screen 3.19: Through this parameter, it is possible to choose
•
whether the equipment bypass is enabled, in cases where the
inverter stops (due to an alarm, or due to manual operation):
"YES": The static bypass will be connected to the output
when the inverter stops. ATTENTION: it is possible to
exceed the power limit established for the input.
"NO": The output will be disconnected (without any
power to the loads) when the inverter stops. ATTENTION:
loads will stop.
7.3.5. ''ALARMS'' level (menu screen 4.0). See Fig
48.
By means of key () active alarms are displayed, being able to
move from one to another inside of the alarm list with the keys
() or ().
()
Port 0 Baud Rate
()
9600 Bauds
screen 3.3
()
Port 0 Protocol
()
SEC
screen 3.6
()
Autom. Battery Test
()
Hour:Minutes: 12:00
screen 3.17
()
()
SALICRU