Faults, causes, remedies
Code
Fault
The sensor source is not correctly configured. In the context menu there is a
link for configuring the sensor source.
Sensor source not avail-
able.
621
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
Setpoint source not
suitably configured.
641
The setpoint source for the cooling function is not correctly configured. In
the context menu there is a link for configuring the setpoint source.
Setpoint source not
available.
642
The setpoint source for the cooling function or the CIF module is not cor-
rectly configured. In the context menu there are links for configuration.
Sensor source not suit-
ably configured.
643
The sensor source for the cooling function is not correctly configured. In the
context menu there is a link for configuring the sensor source.
Same sensor source not
possible.
644
The sensor sources for the cooling function are not correctly configured. In
the context menu there is a link for configuring the sensor sources.
Sensor source not avail-
able.
646
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
Sensor source not suit-
ably configured.
647
The sensor source for the cooling function is not correctly configured. In the
context menu there is a link for configuring the sensor source.
Sensor source not avail-
able.
649
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
1)
No MFA
partner pump
650
1)
MFA
collects the requirement of configured partner pumps to supply in
total. For this purpose, the partner pumps must be selected in the MFA
figuration.
Table 49: Configuration warnings
1)
MFA= Multi-Flow Adaptation
Cause
Remedy
Temperature value
Insert CIF module.
for "Heating/cooling
Activate CIF module.
switchover" is not
connected to existing
CIF module.
Setpoint is not con-
Configure source or
nected to correct
select another source.
source. Input is not
correctly configured.
Setpoint not connec-
Insert CIF module.
ted to existing CIF
Activate CIF module.
module.
Sensor 1 is not con-
Configure source.
nected to correct
Select other source.
source. Input is not
correctly configured.
Sensor sources are
Configure a sensor source
configured to the
to another source.
same source.
Sensor value is not
Insert CIF module.
connected to existing
Activate CIF module.
CIF module.
Sensor 2 is not con-
Configure source or
nected to correct
select another source.
source. Input is not
correctly configured.
Sensor value 2 is not
Insert CIF module.
connected to existing
Activate CIF module.
CIF module.
1)
MFA
is selected, but
Configuration of MFA
no partner pump is
partner pumps is required
configured.
or select another control
mode.
1)
1)
con-
WILO SE 2018-11