Wilo Stratos MAXO-D 32/0,5-12 Notice De Montage Et De Mise En Service page 190

Masquer les pouces Voir aussi pour Stratos MAXO-D 32/0,5-12:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 220
en
190
Communication interfaces: Setting and function
Optional cable break detection
Analogue input (AI2)
Switched off
Switched on
Fig. 71: Optional cable break detection
Select "Switched off" to switch off cable break detection.
Select "Switched on" to activate cable break detection only within an adjustable limit
value.
Optional cable break detection
Analogue input (AI2)
Switched off
Switched on
Limit value
Fig. 72: Cable break limit value
Define limit value for cable break by turning the operating button and confirm by
pressing it.
In the next step define whether
▪ the analogue signal only changes the setpoint
▪ and the pump is additionally switched off through the analogue signal.
A setpoint change can be done through analogue signals without switching on and off
the pump through the signals. In this case, "Switched off" is selected.
If the "On/off by analogue signal" function is switched on, the limit values must be
defined for the switch on/off.
Subsequently assign the MIN signal/value and MAX signal/value.
Signal strength below
the set limit value
is interpreted as
a cable break.
Signal strength below
the set limit value
is interpreted as
a cable break.
WILO SE 2018-11

Publicité

Table des Matières
loading

Table des Matières