Malfunctions - Burkert 2301 Manuel D'utilisation

Vanne de réglage à siège droit 2/2 voies
Masquer les pouces Voir aussi pour 2301:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Malfunctions

11.
MaLfuncTiOns
malfunction
remedial action
Actuator does
Pilot air port interchanged
not switch.
CFA:
Connecting pilot air port 1
CFB:
Connecting pilot air port 1
CFI
Pilot air port 1: Open
Pilot air port 2: Close
Pilot pressure too low
See pressure specifications on the type label.
Medium pressure too high
See pressure specifications on the type label.
Flow direction reversed
See direction arrow on the body.
Type 2301
12)
malfunction
remedial action
Valve is not
Dirt between seal and valve seat
sealed.
Installing dirt trap
Seat seal worn
Installing a new control cone
Flow direction reversed
See direction arrow on the body.
Medium pressure too high
See pressure specifications on the type label.
Pilot pressure too low
See pressure specifications on the type label.
Valve is leaking
Packing gland worn
on the release
Replacing packing gland.
bore.
Tab. 17: Malfunctions
See diagram "Fig. 14: Pneumatic Connection" in the chapter of
12)
the same name.
english
39

Publicité

Table des Matières
loading