install the actuator (with control unit) on the valve body
Check the graphite seal and if required, replace it.
Warning!
danger if incorrect lubricants used!
Unsuitable lubricant may contaminate the medium. In oxygen
applications there is a risk of an explosion!
• In specific applications, e.g. oxygen or analysis applications, use
appropriately authorised lubricants only.
Grease nipple thread before re-installing the actuator (e.g. with
Klüber paste UH1 96-402 from Klüber).
note!
damage to the seat seal or the seat contour!
• When installing the actuator, ensure that the valve is in open
position.
control function a:
Without unit control: pressurize the pilot air port 1 with com-
pressed air (5 bar): valve opens.
With unit control: open the valve according to the operating
instructions for the control unit.
Screw actuator into the valve body.
Observe tightening torque (see „Tab. 14: Tightening torques of
valve body / nipples").
34
english
Type 2301
Maintenance, Cleaning
Pilot air port
Fig. 20: Connections
tightening torques of valve body / nipples
dn
tightening torques [nm]
13/15
45 ±3
20
50 ±3
25
60 ±3
32
65 ±3
40
50
70 ±3
Tab. 14: Tightening torques of valve body / nipples
If the position of the pilot air ports for installation of the
hoses is unfavourable, these can be aligned steplessly by
rotating the actuator through 360°.
The procedure is described in the chapter entitled „8.3.4.
Rotating the actuator".