AC Voltage Derat-
ing:
Fault Ride Through:

Version

Display of version number and serial number of the PC boards installed in the in-
verter (e.g., for service purposes)
Display range
Status
ON/OFF voltage-dependent power reduction
GVDPRe
Threshold from which the voltage-dependent power re-
duction begins
GVDPRv
Reduction gradient used to reduce the power. Example:
10% per volt exceeding the GVDPRe threshold.
Message
Allows info messages to be sent via Fronius Solar Net
Status – default setting: OFF
If the function is activated, the inverter does not switch
off immediately when a short-term interruption to the
AC voltage occurs (outside of the limits set by the grid
supplier); instead it continues to supply power for a
defined time.
DB min – default setting: 90%
"Dead Band Minimum" setting (%)
DB max – default setting: 120%
"Dead Band Maximum" setting (%)
k-Fac. default setting: 0
Display/Display Software/Integrity Checksum/Memory
Card/Memory Card #1/Power Stage/Power Stage Soft-
ware/EMI Filter/Power Stage #3/Power Stage #4
35