Télécharger Imprimer la page

Burkert 8400 Manuel D'utilisation page 35

Masquer les pouces Voir aussi pour 8400:

Publicité

Les langues disponibles

Les langues disponibles

Adjustment and functionalities
9.8.
Description of the function
Function
Description of the function
EXT
• To calibrate the expansion board in transmitters if it is activated (see Calibration Mode chapter 9.7):
Adjust the 4...20 mA output or the 4...20 mA input respectively:
→ Select
OUT
The transmitter generates a 4 mA current.
→ Using a multimeter, measure the current on the 4...20 mA output or input respectively.
→ Input this value in the function
→ Press ENTER to confirm.
The transmitter generates a 20 mA current.
→ Using a multimeter, measure the current on the 4...20 mA output or input respectively.
→ Input this value in the function
→ Confirm or do not confirm the input values by hitting "
SIM
• To test the commutation thresholds by inputting a temperature value.
END
• To go back to Read mode and display the temperature measured.
Type 8400
or
respectively and confirm.
IN
.
OFFS
.
SPAN
" or "
".
YES OK
NO OK
english
35

Publicité

loading