Tab. 2:
Electrical data for transmitters
4...20 mA input
• Linearity error
• Repeatability error
• Max. input impedance
• Protection against
polarity reversals and
overcurrents
• Galvanically insulated
4...20 mA output
• Accuracy
• Wire connection
• Loop resistance
• Galvanically insulated
Relay output on the
transmitters
Type 8400
Technical data
Risk of destroying the
4...20 mA input.
▶Limit the input voltage
to +48 V
• ± 0.2 %
• ± 0.2 %
• 250 W
• yes
• yes
• ± 0.1 % of the full scale
(−3.7 % and +0.7 % of the full
scale if there are disruptions as
per the EN 50082.2 standard)
• 2 wires
• 1100 W to 32 V, 800 W to 24 V,
500 W to 18 V
• yes
Max. 48 V AC, max. 3 A
or 30 V DC, max. 3 A;
programmable
6.3.4. Electrical connections
Version
Connection type
Detector with
M12 female 5-pin connector (not provided).
transistor output
Detector with
EN 175301-803 (type 2518 provided)
relay output
M12, 5-pin female connectors (not provided)
Transmitter
EN 175301-803 (type 2518 provided)
M12, 8-pin female connectors (not provided)
1)
EaseOn with 2511 connector on request
Type of
Cable type
connector
M12 with order
• shielded
code 917116
• 3...6.5 mm in diameter
• with wires with a max. cross section of
0.75 mm
2518 with order
• shielded
code 572264
• 6...7 mm in diameter
• with wires with a cross section of
0.25...1.5 mm
english
and
1)
and
1)
2
2
13