2" (5,1) max.
protusion from wall
for gas or electrical supply
The surface of the entire back wall above the range and below the hood must be covered with a noncombustible material.
*Consult local code for exact location requirements.
OPENING WIDTH
Range 36"
Minimum clearances:
Above cooking surface (above 36" [91.4 cm])
• Sides - 6" (15.2 cm)
• Within 6" (15.2 cm) side clearance, wall cabinets no
deeper than 13" (33.0 cm) must be minimum 18" (45.7
cm) above cooking surface
• Rear - 0" with 9 " backguard; 0" with non-combustible
rear wall.
Below cooking surface (36" [91.4 cm] and below)
• Install with zero clearance between adjacent combustible
construction below the cooking surface and the back
and sides of the appliance.
CAUTION
Pro style gas ranges exhaust oven combustion air through
the rear back guard. Therefore certain cooking conditions
may result in staining or discoloration of the backsplash.
Always choose a back splash material that is suitable
for this application as Fulgor Milano will not be held
responsible for the discoloration of back splash.
4 - Product Dimensions and Cutout Requirements
CUTOUT REQUIREMENTS
min 25 1/2" (65)
Minimum to
Combustibles
or to botton of
ventilation hood
min 18" (45,7)
min 6" (15,2)
3" ( 9 )
GAS
A & B
36"
(91.4)
B
max 13" (33)
min 18" (45,7)
A
min 6" (15,2)
3" ( 9 )
ELECTRIC
min 4 3/4" (12,3)
ADDITIONAL CLEARANCES:
For island installation, maintain 2-½ in. minimum from
cutout to back edge of countertop and 3 in. minimum from
cutout to side edges of countertop (see top view).
For island installation, 12" (305) minimum clearance back
of range to combustible rear wall above countertop.
FLUSH ISLAND INSTALLATION
min 3" (7.6)
BACK
min 2 1/2" (6.3)
min 3" (7.6)
EN
9