7.2
Settings / control actions
Individual control actions can be performed by tapping the sensor surfaces marked with LEDs or with finger movements on the
sensor wheel. When you have worked through the START menu and the system has started up, the system's status can be precisely
monitored using various operational indicators (1 to 3) including statistical analysis of the system values. The basic menu structure
can be found in Appendix 3 of this document.
It is possible to change the existing settings via the CONFIGURATION after "START". As the change to the top-up control type is
a basic configuration and possibly also defined by the equipment level, this is only possible via the START menu. To this end, the
system is stopped when the "Reset Start menu" item is selected in CONFIGURATION, and a new version of the START menu is
worked through based on appropriate prompts. (For this purpose it may be necessary to repeat the pressure settings as they may
have been reset to the factory settings.)
7.3
Recommissioning
Recommissioning (e.g., after extended periods of inactivity / shutdown and maintenance) assumes that the system is free from leaks
and correctly connected electrically. After extended downtimes it is advisable to perform maintenance before recommissioning.
7.3.1 Visual check of the temperature contact sensor - check assembly
For the Vacumat Eco to function correctly, it is essential that the temperature sensor (Pos. 9 in the system diagram) has a reliable,
fixed contact with the pump body through the tensioning strap that attaches it to the pump body. It is also very important that
the temperature contact sensor is sufficiently shielded against ambient temperatures with the sensor insulation (pos 17).
This must always be checked during commissioning, system inspection, servicing or maintenance!
7.4
Explanations relating to the SPC m1 control menu
Explanations relating to the SPC m1
control menu Testing data points
Menu item 2: Data transfer
Menu item 3: Date / time
Menu item 4: Language
Menu item 5: Log in
Menu item 6: Logout
Menu item 7:
Menu item 8: Configuration
Degassing modes 8-1:
Default
Optional
Top-up 8-2:
Top-up capacity 8-2-1-3:
Parameter list 8-2-2:
Pressure 8-3:
Pressure settings 8-3-1:
Error messages 8-5:
Reset Start menu 8-6:
also includes a vacuum test.
makes it possible to perform software updates for the SD card via the
extension module or to read data.
must be used to set the correct time on the control unit. (The system
clock is battery buffered and lasts for about 10 years without a mains
connection.)
can be selected to choose a language for communicating with the control
unit from up to twenty different languages.
supports the entry of access codes in order for service staff to carry out
settings, including setting internal Flamco parameters.
supports logging out after using access codes.
Inaccessible for the customer / operator.
allows users to set or change the different defaults that are relevant for
operating the system.
→ Fully automatic
(setting up) (software default) Only top-up is possible here!
→ Standby
for degassing. Night time breaks can be set up, for example.
Blocking times
Check degassing type. Check for gas residual solution content:
Check degassing
8 ml/l of air = MAX
12 ml/l of air = MED
15 ml/l of air = MIN
Pre configuration 50 L (when pulse water meter and make up are
configurared by the Sales Engineer or service Department).
Accept / edit top-up defaults.
Default → Edit factory settings. *
Default → 16 group error messages not on contact.
→ Activate editing mode!