.6 Possible switching modes of the 8032
hysteresis mode
The change of state occurs when a threshold is detected
(increasing flow rate: high threshold (OHI) to be detected,
decreasing flow rate: low threshold (OLO) to be detected).
Contact
Not inverted
ON
Flow rate
OFF
OLO OHI
window mode
The change of state occurs when any thres-
hold is detected.
Contact
Not inverted
ON
OFF
Flow rate
OLO OHI
the delay (del) is set for the both switching
thresholds. the switching only occurs when
either threshold value (ohi - olo) is excee-
ded for a duration higher than the del delay.
8032
Contact
Inverted
ON
Flow rate
OFF
OLO OHI
Contact
Inverted
ON
OFF
Flow rate
OLO OHI
Flow rate
OHI
OLO
Not inverted
hysteresis mode
Inverted
DEL = 0 s
Not inverted
Inverted
DEL = 2 s
window mode
Not inverted
Inverted
DEL = 0 s
Not inverted
Inverted
DEL = 2 s
switching examples of the 8032
depending on the flow rate and the
switching mode chosen
1
2 s
2 s
OUT
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
2 s
t
Time