5. WiriNG

5.1. General wiring diagram

It is the installer's responsibility to ensure that the automatic installation
and its operation are compliant with the standards in force.
Prior to operate the motorization it is mandatory to install the safety devices required
by EN12453 standard, i.e photocells and self-tested active safety edge (e.g Bircher
Reglomat sensitive edge type ELE040/080A0J0 + control type ESA 25).
After installing the safety edge, it is necessary to perform a force measurement with
a measurement tool compliant with the requirement of section 5.1.1 of EN12445
standard.
No movement is possible before wiring of these safety devices.
PhotoElECtriC
CELLULES
TX
CElls
PHOTOELECTRIQUES
disCoNNECt
thE PoWEr
suPPly BEforE
oPEratiNG oN thE
CoNNECtioNs
GatE oPEN
VOYANT PORTAIL
iNdiCator
OUVERT
terminals
Connections
1-2
Power supply
3-4
Orange light
3-5
Area lighting
6-7-8
Motor
9-10
Accessories power supply
10 -11-16-20
Shared
12
Safety edge
13
Closing end limit
14
Opening end limit
15
Photoelectric cells
17
Stop control
18
Pedestrian open/close control
or
Open only
19
Open/close control
or
Close only
21-22
Aerial
SPIA (MR/08
Gate open signal
module)
Copyright © 2011 Somfy SAS. All rights reserved.
RX
NC
C1 C2
230V~ ±10%
mr/08 rElay
MODULE MR/08
modulE
description
230 V~ ±10%, 50-60 Hz board power supply input
Orange non flashing light output 230 V - 50 W max.
Area lighting output 230 V - 100 W max.
Motor connection
Accessories power supply output 24 V - 500 mA (9 = +, 10 = -)
Input shared terminals
Safety edge input (NC switch)
Closing end limit switch (NC switch with gate in intermediate position)
Opening end limit switch (NC switch with gate in intermediate position)
With dip1 SW2 OFF: photoelectric cell input only active when closed (NC switch)
With dip1 SW2 ON: photoelectric cell input active when open and closed (NC switch)
Stop control input (NC switch). Pressing this control blocks operation of the motors.
Pressing it during the pause time with the gate open cancels automatic closing.
Pedestrian open control input (NO switch) controls the opening of the gate by
approximately 1 m and closing in step by step mode.
See page 15 to switch to "Open only"
Open/close control input (NO switch) controls the opening and closing in step by step
mode.
See page 15 to switch to "Close only"
Aerial input (21 = core, 22 = braid)
Output - NO potential-free contact - disconnection capacity 230V 3A
20
NO
oPEN/ClosE // ClosE oNly
19
OUVRE/FERME // FERME SEULEMENT
NO
oPEN PEdEstriaN/ClosE // oPEN oNly
18
OUV. PIÉTONS/FERME // OUVRE SEULEMENT
NC
stoP
17
STOP
16
15
NC
oPENiNG ENd limit
14
FIN DE COURSE OUVERTURE
NC
ClosiNG ENd limit
13
FIN DE COURSE FERMETURE
NC
BARRE PALPEUSE
12
safEty EdGE
11
-
10
9
+
8
sharEd
COMMUN
7
FERME
ClosE
6
OUVRE
oPEN
5
4
3
2
F
50/60Hz
1
N
MASSE
Earth
Elixo 800/1300/2000
20
19
18
17
16
CELLULES
CElls
15
14
13
12
BARRE PALPEUSE
safEty EdGE
11
10
9
8
COMMUN
7
FERME
6
OUVRE
5
4
3
2
1
22
21
ANTENNE
aErial
9