6.4 REGULATIONS
Compressor
The compressor can be active only in START function when the room probe has no error.
If the presence of door is on (PI=I), the door must be closed to permit the starting of the compressor only
if P6=0. With P6=0 the compressor is active even if the door is open and with arrested fan. The compressor
starts according to the SET POINT on, corresponding to the selected cycle and according to the differential of
temperature set (Parameter P8).
The protection time for the compressor are:
P9: minimum delay that must exist between the switching off and the next starting up of the compressor.
This parameter is used also like reset of the card.
P10: minimum delay that must exist between 2 consecutive starting ups of the compressor.
Manual defrosting
The defrosting is carried out with open door, without the use of neither the heater nor the hot gas.
Parameters
Pressing contemporarily Up
At this point on the display appears the number itself of the parameter (P0). Pressing the SET
sible to see the value of the parameter itself and modify it.
THE KEYS UP
AND DOWN
VALUE OF THE PARAMETER IS ON, THEY MODIFY IT.
Par.
P0
When switching to conservation the buzzer sounds for secs. indicated
P1 Door present 0=door absent; 1=door present
P2 Fan during the process 0=together with the compressor 1=always on
P3 Permit to enter the core probe function
P4 Permit to enter the negative process
P5 Permit to enter the defrosting
P6 Stopping functions when the door is open 0=compressor+fans; 1=fans
P7 Configuration RL2 0=defrosting: I=fan+defrosting
P8 Hysteresis of regulation
P9 Protection of the compressor Off/On (also valid as reset)
P10 Protection of the compressor On/On
P11 Defrosting duration
P12 Dripping duration
P13 Core probe for the positive process
P14 Core probe for the negative process
P15 Room probe for the positive process
P16 Room probe for the negative process
P17 Room probe for the positive conservation process
P18 Room probe for the negative conservation process
P19 Positive time process duration
P20 Negative time process duration
P21 Set condenser temperature for second fan
P22 Enable controller for secondary fan
P23 Relay 4 configuration; 0 = disabled; 1 = UV lamp;
2 = Probe heating; 3 = 3rd condenser fan
P24 Sterilization duration setting
P25 Sterilization temperature threshold setting
P26 3 ° condenser fan temperature threshold setting
P27 Pressure switch setting. 0 = pressure switch disabled;
1,2,3,4 = alarm counting before locking the loads
P28 Probe heating duration setting
P29 Probe heating temperature set point
and Down
, WHEN THE PARAMETER SETTING IS ON, ALLOW TO PASS TO THE NEXT/FORMER PARAMETER; WHEN THE
Description
Blast chillers | User and maintenance manual | EN
to enter the parameter setting for at least 4 sec.
key, it is pos-
Def.
Def.
Min
Max
4R
3R
0
1
10
10
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
1
20
3
0
99
2
0
99
3
0
99
10
10
0
99
3
-50
99
3
-50
99
-18
-18
-50
99
-2
-50
99
-35
-35
-50
99
0
-50
99
-25
-25
0
599
89
89
0
599
270
270
-50
99
34
34
1
0
1
0
3
3
1
999
15
15
-50
99
5
-50
99
36
36
0
4
0
1
10
2
0
90
4
Unit
1
1
1
1
1
1
1
3
°C
2
min
3
min
min
3
min
3
°C
°C
-2
°C
°C
0
°C
°C
Min
Min
°C
1
0
Min
5
°C
°C
0
2
Min
4
°C
43