Electrical Connection; Schematic Wiring Diagram For Ecolite Condensing Units - Bitzer LHL3E/2EES-2Y Instructions De Service

Masquer les pouces Voir aussi pour LHL3E/2EES-2Y:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7 Electrical connection

Semi-hermetic compressor, condenser fan and elec-
trical accessories correspond to the EU Low Voltage
Directive 2014/35/EU.
The ECOLITE condensing unit is provided exclusively
for the connection to TN-C-S or TN-S three-phase
power supply systems with a nominal voltage 230/400
V Δ/Y at a nominal frequency of 50 Hz. The connection
of a neutral conductor is mandatory. A nominal supply
voltage with qualitative characteristics according to DIN
EN 50160 is required. The ECOLITE condensing unit is
provided for a stationary installation.
Type gG fuses or line protection switches with C char-
acteristic must be provided.
Type
LHL3E/2EES-2(Y)
LHL3E/2DES-2(Y)
LHL3E/2CES-3(Y)
LHL5E/4FES-3(Y)
LHL5E/4EES-4(Y)
LHL5E/4DES-5(Y)
LHL5E/4CES-6(Y)
Depending on local conditions and applicable regula-
tions, a supply disconnecting device must be provided
on site. The service switch provided in the ECOLITE
condensing unit does normally not fulfil the require-
ments regarding an electrical disconnection of the
device.
KB-206-2
Recom-
Motor pro-
mended
tection
fuse
switch set-
ting value
8 A
8.0 A
10 A
9.5 A
13 A
11.0 A
13 A
11.5 A
16 A
14.5 A
16 A
16.0 A
20 A
20.0 A
7.1 Schematic wiring diagram for ECOLITE
condensing units
Abbr.
Component
B1
Controller
B3
High pressure transmitter (liquid line)
B4
Low pressure transmitter (suction gas
line)
C1
Operating capacitor fan 1
C2
Operating capacitor fan 2
F2
Fuse rating 230 V
F3
Control circuit fuse
F5
High pressure switch
F6
Low pressure switch
K1
Main contactor
M1
Compressor
M1E
Oil heater
M1Y1
CRII SV1
M1Y2
CRII MV2 (option)
M2
Fan 1
M3
Fan 2
M4
Additional fan
N2
Fan control module
OLC-K1
Oil monitoring (option)
Q1
Service switch
R3
Discharge gas temperature sensor
R4
Ambient temperature sensor
R5
Cold store temperature sensor (option)
R8
Suction gas temperature sensor
SE-B1
Protection device
S12
Door switch
T1
Control transformer
V1
Fan control module
Tab. 5: Legend schematic wiring diagram ECOLITE
53