Monitoring of the application limits – menu ALr:
Menu item
F2+F4⇒PAr⇒EMO⇒dHA
Modbus: 16426
F2+F4⇒PAr⇒EMO⇒dHd
Modbus: 16427
F2+F4⇒PAr⇒EMO⇒SLA
Modbus: 16428
F2+F4⇒PAr⇒EMO⇒SLd
Modbus: 16429
The ECOLITE controller monitors certain application
limits of the compressor or switches the compressor off
to protect it as soon as the application limits are ex-
ceeded.
REF
R404A
R134a
dHA
62°C
70°C
When changing the refrigerant type (parameter Ert), the
ECOLITE controller sets the parameter SLA to the fol-
lowing presetting for the different refrigerants:
REF
R404A
R134a
SLA
-45°C
-25°C
If the cold store control is active, monitoring of the min-
imum and maximum overheating of the suction gas is
not possible and therefore deactivated.
72
Function
Maximum condensing pressure (software high pressure switch)
0.0 – 100.0 °C
Ex-factory setting: 62.0 °C
Hysteresis at the max. condensing pressure (software high pressure switch)
0.0 – 10.0 K
Ex-factory setting: 5.0 K
Minimum suction pressure (software low pressure switch)
-60.0 – 50.0 °C
Ex-factory setting: -45.0 °C
Hysteresis at the min. suction pressure (software low pressure switch)
0.0 – 10.0 K
Ex-factory setting: 5.0 K
R407C
R507A
R407A
55°C
62°C
60°C
R407C
R507A
R407A
-25°C
-45°C
-40°C
When changing the refrigerant type (parameter Ert), the
ECOLITE controller sets the parameter dHA to the fol-
lowing presetting for the different refrigerants:
R407F
R450A
60°C
70°C
R407F
R450A
-40°C
-25°C
R448A
R513A
R449A
60°C
70°C
60°C
R448A
R513A
R449A
-40°C
-25°C
-40°C