8.1.4

Status menu

Menu item
F4⇒init⇒OnOF
Modbus: 16467
(read and write)
Display of the active set points:
They can only be displayed after entering a password
(see chapter Programming menu, page 67).
Menu item
F4⇒SEt⇒SP1
Modbus: 16388
(read and write)
F4⇒SEt⇒SP2
Modbus: 16407
(read and write)
F4⇒SEt⇒SP3
Modbus: 16408
(read and write)
F4⇒SEt⇒SP4
Modbus: 16424
(read and write)
60
Function
Activation / deactivation of the ECOLITE controller
OFF = controller deactivated
On = controller activated
Ex-factory setting: OFF = controller deactivated
Function
Set point of suction pressure controller
-45.0 – 22.5°C
Ex-factory setting: -10.0 °C
Set point of condensing pressure controller (without correction)
10.0 – 80.0 °C
Ex-factory setting: 30.0 °C
Maximum condensing pressure
10.0 – 80.0 °C
Setting ex factory: 60.0 °C
Set point of cold store temperature controller
-40.0 – 22.5°C
Setting ex factory: 2.0 °C