If the ECOLITE condensing unit is mounted on mount-
ing brackets, the installation surface under the four lat-
eral fixing points must be at least 6 x 6 cm. Use three
mounting brackets (on the right, in the middle and on
the left). It is not necessary to screw the bracket in the
middle to the device.
NOTICE
!
!
When installing the condensing unit in areas
where extreme wind loads may occur, screw it
always firmly to the ground!
If installed on a roof, provide sufficient lightning
protection!
CAUTION
The fins of the condenser have sharp edges!
Risk of lacerations.
Before performing any work on the condensing
unit: Wear protective gloves.
30 cm
200 cm
Fig. 6: Minimum distances to the wall and ceiling (example shows
LHL5E/ .. )
50
50 cm
≥ 30 cm
25 cm
200 cm
Fig. 7: Minimum distances to the wall and ceiling when mounted on a
mounting bracket (example shows LHL5E/ ..)
30 cm
Fig. 8: Minimum distances when installing several condensing units
50 cm
≥ 6 cm
≥ 25 cm
50 cm
≥ 100 cm
KB-206-2