6.11.5 Serial line terminations
To set the serial line terminations operate on DIP
1.
The board has two DIP switches used to configure the
serial line terminations (120 Ohm) (Tab. 9, page 21).
Every peripheral that is situated at the end of a line
must be terminated using the appropriate dip-switch
in order to prevent signal reflection and distortion.
SERIAL LINE TERMINATIONS (DIP 1)
Serial line
–
–
terminations
–
–
–
ON –
–
OFF –
Tab. 9
MNVCUCT_1511_EN
ON RS-485-2 line, termination
enabled
OFF RS-485-2 line, termination
disabled
RS-485-1 line, termination
enabled
RS-485-1 line, termination
disabled
6.11.6 Protocol configuration
The protocol must be set to NETWORK in
case of versions with digital video encoder.
To set the protocol operate on DIP 3.
The Pan & Tilt can be controlled via various protocols.
PROTOCOL CONFIGURATION (DIP 3)
SW 1 SW 2 SW 3 SW 4 Configuration
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Tab. 10
6.11.7 Address configuration
To set the address operate on DIP 2.
It is possible to set the pan & tilt address: from 1 a
1023. Binary code is used to select the address, using
the dip-switches (A Appendix - Address table, page
65).
AMERICAN DYNAMICS
ERNITEC
NETWORK
PANASONIC
PELCO D
VIDEOTEC MACRO
21