10.3. electrical installation with cable gland
Danger!
risk of electric shock!
• Before reaching into the device or the equipment, switch off the power supply and secure to prevent reactivation!
• Observe applicable accident prevention and safety regulations for electrical equipment!
10.3.1. designation of the screw-type terminals
Figure 29:
Connection of screw-type terminals
10.3.2. connection of the positioner Type 8694
→
The screw-type terminals can be accessed by unscrewing the body casing (stainless steel).
→
Push the cables through the cable gland.
→
Connect the positioner according to the following tables:
input signals from the control centre (e.g. PLC)
terminal configuration
4
Set-point value +
5
Set-point value GND
1
Binary input +
Table 18:
Assignment of screw-type terminals - input signals of the control center - cable gland
Option only
16)
46
English
Type 8694
Electrical installation 24 V DC
1
2
16)
3
16)
4
5
6
7
external circuit
4
+ (0/4 ... 20 mA)
5
GND
1
+
with reference to terminal 7 (GND)
0 ... 5 V
(log. 0)
10 ... 30 V (log. 1)