Type 8694
Electrical installation 24 V DC
output signals to the control center (e.g. PLC; for analog output option only)
terminal configuration
Analogue position feedback +
2
3
Analogue position feedback GND
Table 19:
Assignment of screw-type terminals - output signals to the control center - cable gland
electrical supply voltage
terminal configuration
6
Supply voltage +
7
Supply voltage GND
Table 20:
Assignment of screw-type terminals - Supply voltage - cable gland
Figure 30:
Position of the seal in the body casing
Check that the seal is correctly positioned in the body casing.
noTe!
damage or malfunction due to penetration of dirt and humidity!
To ensure protection class IP65 / IP67:
• Tighten the union nut on the cable gland according to the cable size or dummy plugs used (approx. 1.5 Nm).
• Screw the body casing in all the way.
Tighten union nut on the cable gland (torque approx. 1.5 Nm).
Close the device (assembly tool: 674077
When the power supply is applied, the positioner is operating.
Make the required basic settings and actuate the automatic adjustment of the positioner, as described in the
chapter entitled "12. Start-up".
The assembly tool (674077) is available from your Bürkert sales office.
17)
external circuit
2
3
external circuit
6
7
Body casing
Seal
body casing
).
17)
+ (0/4 ... 20 mA)
not galvanically isolated
GND
24 V DC ± 10 %
max. residual ripple 10 %