4.1. Power circuits

4.1.1. Standard connection priority source on switch i
The product is delivered from the factory with the following configuration:
1
• the source
on control module (connectors 101 to 106) is linked to switch I
2
• the source
on the control module (connectors 201 to 206) is linked to switch II.
In case of voltage sensing and power supply kit mounting on ATyS 6, mount the kit before power cables
connections.
4.1.1-1
Load
Source
1
Source
2
4.1.2. Connections
Take into account connection cables length for section selection.
(A)
Minimum cables
section Cu (mm
) at Ith
2
Minimum bars section
Cu (mm
) at Ith
2
Maximum cables
section Cu (mm
)
2
Maximum bars width
Cu (mm) at Ith
4.1.2-1
86
ATyS 3e, 6e, 6s - Ref.: 531 848 G GB
1
2
125
160
250
400
35
50
95
185
-
-
-
-
50
95
150
240
20
20
32
32
3e 6s 6e
4.1.1-2
630
800
1000
1250
2x150 2x185
-
2 x 30 x 5 2 x 40 x 5 2 x 60 x 5 2 x 60 x 5 2 x 80 x 5 2x100x10 2x100x10 2x100x10
2x300 2x300 4x185 4x185 6x185
50
63
63
63
Recommended tightning torque
M6: 4.5 N.m
M8: 8.3 N.m
M10: 20 N.m
M12: 40 N.m
Maximum tightning torque
M6: 5.4 N.m
M8: 13 N.m
M10: 26 N.m
M12: 45 N.m
ii
i
1600
2000
2500
-
-
-
-
-
-
100
100
100
3200
-
-
100