7.4. Operation

7.4.1. presentation
This mode allows in manual position (not padlocked) to start a test off load. In the automatic position, it allows the starting of a test,
on or off load and to control electricaly the position of the changeover switch on ATyS 6e.
7.4.1-1
enter operation mode
• Step 1: press and hold the "mode" push button for 5 s
• Step 2: enter the operation code (CE) using navigation push buttons (code 4000)
• Step 3: press "validation" push button
7.4.1-2
exit operation mode
Press and hold for 5 s "mode" push button
7.4.1-3
navigate in operation mode
• Press "mode" push button to access different features
• Press "validation" push button to activate required function
7.4.2. operation mode architecture
7.4.2-1
Led "test on load"
Led "test off load"
Led "control"
is blinking
* only on ATyS 6e.
118
ATyS 3e, 6e, 6s - Ref.: 531 848 G GB
Yes, press
"validation"
is blinking
1 2
No, press
"mode"
Yes, press
"validation"
is blinking
1 2
No, press
"mode"
Yes, press
"validation"
1 2
No,
press "mode"
7. opEratIoN atyS 6s and 6e
Enter: press 5 seconds
Led "TEST ON LOAD"
is fixed
Led "TEST OFF LOAD"
is fixed
Led "CONTROL 1 O 2 "
is fixed
Exit: press 5 seconds
TEST ON LOAD
Loss of priority
source sequence
TEST OFF LOAD
Genset start
sequence
Changeover switch
Led "contrôle"
position control 1 O 2
fixe
(PS1, PS 0, PS2)