7.3. Programming
7.3.3. parameters characteristics (cont.)
Menu Volt
1 2
Threshold detection starts from the loss of source or source return sequence.
7.3.3-1
%
Controlled value (voltages)
100
LCD
Denomination / Definition
Network 1 over voltage threshold
1 2
Network 1 over voltage threshold hysteresis
1 2
Network 1 under voltage threshold
1 2
Network 1 under voltage threshold hysteresis
1 2
Network 2 over voltage threshold
1 2
Network 2 over voltage threshold hysteresis
1 2
Network 2 under voltage threshold
1 2
Network 2 under voltage threshold hysteresis
1 2
Hysteresis values range is limited by thresholds values.
(cont.)
7. opEratIoN atyS 6s and 6e
Over voltage threshold (oU)
Over voltage hysteresys
threshold (oUh)
Available source
t
Under voltage hysteresys
threshold (uUh)
Under voltage threshold (uU)
Setting range
from 102 to
120 %
from 101 to
119 % (<oU)
from 80 to
98 %
from 81 to
99 % (>uO)
from 102 to
120 %
from 101 to
119 % (<oU)
from 80 to
98 %
from 81 to
99 % (>uU)
ATyS 3e, 6e, 6s - Ref.: 531 848 G GB
Default values
115 %
110 %
85 %
95 %
115 %
110 %
85 %
95 %
113