7.3. Programming (cont.)
7.3.3. parameters characteristics (cont.)
Menu Timer
1 2
LCD
Denomination
Main Failure
Timer
1 2
Delay on
transfer Timer
1 2
O Main failure
Timer
1 2
Main return
Timer
1 2
O main return
Timer
1 2
Cool down
Timer
1 2
Communication Menu
1 2
Menu only activated in case of optional communication module connection (refer to Options chapter).
LCD
Denomination
Address
1 2
Speed
1 2
Stop bit
1 2
Parity bit
1 2
Definition
Delays priority network failure detection
Standby network stability validation before transfer
Rest in O position when transferring
from main network to standby network
Main network stability validation before re-transfer
Rest in O position when re-transferring from standby network to
main network
Allows generator cooling down period after load's
retransfer from standby source (generator) to Main source
6s 6e
Definition
Address of the device
Communication speed
7. opEratIoN atyS 6s and 6e
Setting range
from 0 to 60 s
from 0 to 60 s
from 0 to 20 s
from 0 to
30 min
from 0 to 20 s
from 0 to
30 min
Setting range
1 to 247
2400, 4800,
9600, 19 200,
38 400
1, 2
No, odd, even
ATyS 3e, 6e, 6s - Ref.: 531 848 G GB
Default values
5 s
5 s
5 s
1 min
5 s
4 min
Default values
5
9 600
1
No
115