7.6. Automatic sequences (cont.)
7.6.3. Return to priority source
This sequence is activated as soon as the changeover switch is in automatic mode and in emergency position (position II) :
1
• the priority source
is not available,
• the changeover switch is in emergency position (ex: genset),
2
• the emergency source
is available.
Specific feature: manual re-transfer
• When priority source comes back, it can be required not to
automatically retransfer and wait for a more adequate timing.
• It is possible, validating manual retransfer feature (refer to
programming), to block the re-transfer.
It is initiated from:
• validation push button localy or on ATyS D20,
• via an input on optional module 2I / 2O on ATyS 6e, Mtf
feature.
7.4.5-2
Sequence description
Generator running (emergency source) &
Main's
return
To loss of priority
source sequence
Priority source unavailable
Switch in position II
Priority
No
source
return?
Manual re-transfer
Yes
MRT = 0
Count down
MRT
Priority source
lost again
before MRT
times out?
Reset MRT
Transfer II
Count Down OMR
Transfer 0
Reset CDT
7. opEratIoN atyS 6s and 6e
7.6.3-1
Mode
Yes
semi-auto
activated ?
(Mtf)
No
Yes
Validation
OMR 0?
Yes
> 0
OMR = 0
> I
Transfer II
Transfer II
Count Down CDT
Loss of priority source
CDT = 0
Stop generator
position 1
Back to priority source control
Manual re-transfert
= validation press
optional input acti-
vation, feature Mtf
Yes
Loss of
priority source ?
No
No
> I
> I
ATyS 3e, 6e, 6s - Ref.: 531 848 G GB
Or
125