7.2. Meaning of the various parameters

(Text in bold = default values)
P0
Operating mode
1: sequential
Values
2: sequential + short closure time-delay (60 s)
3: sequential + long closure time-delay (120 s) + block-
age of cells (2 s)
Comments
P0 = 1: Each press on the remote control button caus-
es the motor to move (initial position: gate closed) as
per the following cycle: open, stop, close, stop, open,
etc.
P0 = 2: This operating mode is only authorised if the
photoelectric cells are installed and P4 = 3.
In sequential mode with short closure time-delay:
• the gate will close automatically a er a time-delay
of 60 s,
• pressing a button on the remote control inter-
rupts the movement taking place and the closure
time-delay (the gate remains open).
P0 = 3: This operating mode is only authorised if the
photoelectric cells are installed and P4 = 3.
In sequential mode with long closure time-delay +
blockage of the cells:
• the gate will close automatically a er a time-delay
of 120 s.
• pressing a button on the remote control inter-
rupts the movement taking place and the closure
time-delay (the gate remains open).
• A er the gate is opened, movement in front of the
cells (safe closure) will close the gate a er a short
time delay (fixed at 2 seconds).
If no movement occurs in front of the cells, the gate
will close automatically a er a time-delay of 120 s.
If there is an obstacle in the cells' detection zone,
the gate will not close. It will close once the obsta-
cle is removed.
P1
Gate speed
Values
1: Slow
2: Standard
3: High speed
Comments
If the parameter has been modified, you are advised to
perform auto-programming again.
Warning
If the parameter has been modified, you must
check that the obstacle detection system
complies with Annex A of standard EN 12 453. If
necessary, install a safety edge and check that
compliance is obtained.
Failure to follow this instruction may result in
serious injury, e.g. due to crushing by the gate.
P2
Opening and closing slowing zone
1: None
Values
2: Short (approx. 20 cm)
3: Long (approx. 60 cm)
Comments
If the parameter has been modified, you are advised to
perform auto-programming again.
Warning
If the parameter has been modified, you must
check that the obstacle detection system
complies with Annex A of standard EN 12 453. If
necessary, install a safety edge and check that
compliance is obtained.
Failure to follow this instruction may result in
serious injury, e.g. due to crushing by the gate.
Copyright © 2018 SOMFY ACTIVITES SA. All rights reserved.
P3
Obstacle detection sensitivity
Values
1: Very low
2: Low
3: Standard
4: Maximum
Comments
If the parameter has been modified, you are advised to
perform auto-programming again.
Warning
If the parameter has been modified, you must
check that the obstacle detection system
complies with Annex A of standard EN 12 453. If
necessary, install a safety edge and check that
compliance is obtained.
Failure to follow this instruction may result in
serious injury, e.g. due to crushing by the gate.
P4
Photoelectric cells
Values
1: Active
2: BUS
3: Active with auto-test via power supply switching
4: Inactive
NB
Comments
It is essential to remove the bridge between ter-
minals 17 and 18, and connect the cells before
modifying parameter P4.
1: safety device without auto-test; it is essential to
check that it is operating correctly every 6 months.
2: bus cells application.
NB
If when confirming P4=2, the P4 and photoelec-
tric cells indicator lights are flashing, there is a
short-circuit on the cells safety input, and the
parameter modification is disregarded. Remove
the bridge between terminals 17 and 18, and
check the cells connection (see 6.2.1 Photoelectric
cells - Fig. 17), set up P4 again and then perform
auto-programming again.
3: the auto-test is run on the device for each operating
cycle via power supply switching.
Warning
It is compulsory to install photoelectric cells
WITH AUTO-TEST P4 = 3 if:
• remote control of the mechanism is used
when the door is not visible,
• automatic closing is activated ("P0" = 2 or 3).
4: the safety input is disregarded.
Warning
If P4 = 4, the drive cannot be operated in auto-
matic mode and in-view control of the drive is
mandatory.
Px
Safety edge auto-test
Values
1: Without auto-test
2: With auto-test
Comments
1: safety device without auto-test; it is essential to
check that it is operating correctly every 6 months.
2: the auto-test is run on the device for each operating
cycle via the test output.