Meaning of different parameters
Code
Description
P01
Complete cycle operating
0: sequential
mode
1: sequential + timed close
2: semi-automatic
3: automatic
4: automatic + cell blocking
5: deadman's control (wire)
P02
Automatic closing time delay
0 to 30 (value x 10 s = time delay value)
in complete operating mode
2: 20 s
P03
Pedestrian cycle operating
0: identical to complete cycle operating mode
mode
1: without automatic closing
2: with automatic closing
P04
Short automatic closing time
0 to 30 (value x 10 s = time delay value)
delay in pedestrian cycle
2: 20 s
P05
Long automatic closing time
0 to 99 (value x 5 min. = time delay value)
delay in pedestrian cycle
0: 0
P06
Pedestrian opening
1: minimum pedestrian opening
amplitude
9: maximum pedestrian opening
2: 80 cm
P07
Cell safety input
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply switching
4: bus cells
P08
Safety edge safety input
0: inactive
1: active
2: active with autotest
P09
Programmable safety input
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply switching
P10
Programmable safety input
0: active closing
- function
1: active opening
2: active closing + ADMAP
3: all movement disabled
P11
Programmable safety input
0: stop
- action
1: stop + partial reversal
2: stop + complete reversal
P12
Orange warning light
0: no warning
1: with 2 s warning prior to movement

Operating codes display

Code
C1
Awaiting command
C2
Gate opening
C3
Awaiting gate closure
C4
Gate closing
C6
Detection in progress for cell safety
C7
Detection in progress for safety edge safety
C8
Detection in progress for programmable safety
C9
Detection in progress for emergency stop safety
C12
Reinjecting current
C13
Safety device autotest in progress
C14
Permanent complete opening wire control input
C15
Permanent pedestrian opening wire control input
C16
BUS cell programming refused
Cc1
9.6 V power supply
Cu1
24 V power supply
Operating codes display
Code
Description
E1
Cell safety autotest fault
E2
Programmable safety autotest fault
E3
Defective safety edge autotest
E4
Obstacle detection when opening
E5
Obstacle detection when closing
E6
Cell safety fault
E7
Safety edge safety fault
E8
Programmable safety fault
E10
Motor short circuit protection
E11
24 V power supply short protection
E12
Hardware fault
E13
Accessories power supply fault
E15
Fault when the control box supplied by the backup
battery is first switched on

Accessing memorised data -

Code
Description
U0 to U1
Complete opening cycle counter
U2 to U3
U6 to U7
Cycle counter with obstacle detection
U8 to U9
U12 to U13
Partial opening cycle counter
U14 to U15
Reset movement counter
U20
Number of remote controls memorised for complete opening control
U21
Number of remote controls memorised for pedestrian opening control
U22
Number of remote controls memorised for remote lighting control
U23
Number of remote controls memorised for auxiliary output control
d0 to d9
Log of the last 10 faults (d0 most recent - d9 oldest)
dd
To clear the fault log: press and hold "OK" for 7 s.
Values (bold = default)
Description
Comments
The cell autotest is not satisfactory.
The programmable safety input autotest is not satisfactory.
The safety edge autotest is not satisfactory.
Detection in progress on safety input for longer than 3 minutes.
Product and additional devices connected to terminals 21 to 26 not
operating
The hardware autotests are not satisfactory
The accessories power supply cuts out following an overload (excessive
consumption)
To access memorised data, select parameter "Ud" then press "OK".
global [hundreds of thousands - tens of thousands - thousands] [hundreds - tens - units]
since last auto-programming [hundreds of thousands - tens of thousands - thousands] [hundreds - tens - units]
global [hundreds of thousands - tens of thousands - thousands] [hundreds - tens - units]
since last auto-programming [hundreds of thousands - tens of thousands - thousands] [hundreds - tens - units]
Code
Description
Setting
P13
Area lighting output
P14
Area lighting time delay
P15
Auxiliary output
P16
Auxiliary output time delay
P19
Closing speed
P20
Opening speed
P21
Closing slowdown zone
P22
Opening slowdown zone
P25
Closing torque limitation
P26
Opening torque limitation
P27
Closing slowdown torque
limitation
P28
Opening slowdown torque
limitation
P33
Obstacle detection sensitivity 0: very low sensitivity
P37
Wired control inputs
P40
Coupling speed when closing
P41
Coupling speed when
opening

Programming codes display

Code
H0
Awaiting setting
Hc1
Awaiting setting + 9.6 V power supply
Hu1
Awaiting setting + 24 V power supply
H1
Awaiting start of auto-programming
H2
Auto-programming mode - opening
H4
Auto-programming mode - closing
F0
Awaiting remote control memorisation for operation in complete opening mode
F1
Awaiting remote control memorisation for operation in pedestrian opening mode
F2
Awaiting remote control memorisation for remote lighting control
F3
Awaiting remote control memorisation for auxiliary output control
Check that "P07" is correctly configured. Check the wiring of the cells.
Check that "P09" is correctly configured. Check the programmable safety input wiring.
Check that "P08" is correctly configured. Check the safety edge wiring.
Check that no obstacles are causing the cells or safety edge to detect.
Check that "P07", "P08" or "P09" is correctly configured in relation to the device connected to the
safety input.
Check the safety device wiring.
Check that the photoelectric cells are correctly aligned.
Check the motor wiring.
Check the wiring, then disconnect the power supply for 10 seconds.
Request a gate movement. If the fault is still present, contact Somfy.
N.B.: maximum accessories consumption = 1.2 A
Check the consumption of the connected accessories.
Disconnect the backup battery and connect the control box to the mains to switch it on for the
first time.
Comments
Values (bold = default)
0: inactive
1: controlled operation
2: automatic + controlled operation
0 to 60 (value x 10 s = time delay value)
6: 60 s
0: inactive
1: automatic: gate open indicator light
2: automatic: timed bistable
3: automatic: one-touch
4: controlled: bistable (ON-OFF)
5: controlled: one-touch
6: controlled: timed bistable
0 to 60 (value x 10 s = time delay value)
6: 60 s
1: slowest speed to
10: highest speed - Default value: 5
1: slowest speed to
10: highest speed - Default value: 5
0: shortest slowdown zone
to
5: longest slowdown zone
Default value: 1
0: shortest slowdown zone
to
5: longest slowdown zone
Default value: 1
1: minimum torque
to
10: maximum torque
Adjusted when auto-programming complete
1: slightly sensitive
2: standard
3: very sensitive
0: complete cycle mode - pedestrian cycle
1: opening mode - closing
1: slowest speed to
4: fastest speed
Default value: 2
Description
Solution?