Mains Choke/Mains Filter Assignment - Lenze 9300 vector Série Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation to UL
Supply conditions
Range
Fuses
Cables
Observe all national and regional regulations!
Operation at rated power
9300
Type
Operation with mains choke/mains filter
EVF9332−xV
EVF9333−xV
5.7.4

Mains choke/mains filter assignment

Operation at rated power
9300
Mains choke
Type
EVF9332−xV
ELN3−0022H130
EVF9333−xV
ELN3−0017H170
Operation with increased rated power
9300
Mains choke
Type
EVF9332−xV
ELN3−0017H170
EVF9333−xV
ELN3−0014H200
EDKVF9333V DE/EN/FR 7.2
Standard devices in the power range 75 ... 90 kW
Description
l
Only according to UL 248
l
Mains short−circuit current up to 10000 A
l
Mains short−circuit current up to 50000 A
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Rated fuse current
Fuse
[A]
175
200
Interference voltage category according to EN 61800−3 and motor cable length
Component
C2
EZN3A0022H150
E82ZN75334B230
EZN3A0017H200
E82ZN90334B230
Interference voltage category according to EN 61800−3 and motor cable length
Component
C2
EZN3A0017H200
E82ZN90334B230
EZN3A0015H230
EZN3A0017H200
l
Electrical installation
Mains choke/mains filter assignment
: All classes permissible
rms
: Only classes "J", "T" or "R" permissible
rms
Cable cross−section
max. [m]
25
E82ZN75334B230
50
EZN3B0022H150
25
E82ZN90334B230
50
EZN3B0017H200
max. [m]
25
E82ZN90334B230
50
EZN3B0017H200
25
EZN3B0015H230
25
EZN3B0017H200
5
L1, L2, L3, PE
[AWG]
2/0
3/0
Component
C1
max. [m]
10
50
10
50
Component
C1
max. [m]
10
50
50
50