Mechanical installation
Standard devices in the power range 0.37 ... 11 kW

Mounting in "cold plate" technique

4.1.4
Mounting in "cold plate" technique
The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on collective coolers.
For this purpose, the drive controllers of type EVF93xx−CV must be used.
Required mounting material from the scope of supply:
Description
Fixing bracket
Sheet metal screw
3.5 × 13 mm (DIN 7981)
Requirements for collective coolers
The following points are important for safe and reliable operation of the controller:
Good thermal connection to the cooler
ƒ
– The contact surface between the collective cooler and the controller must be at
least as large as the cooling plate of the controller.
– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all
specified screw connections.
Observe the thermal resistance R
ƒ
controller operation under rated conditions.
9300
Type
EVF9321−CV
EVF9322−CV
EVF9323−CV
EVF9324−CV
EVF9325−CV
EVF9326−CV
Ambient conditions
The rated data and the derating factors at increased temperature also apply to the
ƒ
ambient temperature of the drive controllers.
Temperature at the cooling plate of the drive controller: max. 75 °C.
ƒ
146
Use
Drive controller fixing
Mounting of fixing bracket to
the drive controller
given in the table. The values are valid for
th
Cooling path
Power to be dissipated
P
[W]
v
24
42
61
105
180
360
l
EVF9321
EVF9323
EVF9322
EVF9324
Quantity
2
2
6
6
Heatsink − environment
R
[K/W]
th
1.45
0.85
0.57
0.33
0.19
0.10
EDKVF9333V DE/EN/FR 7.2
EVF9325
EVF9326
2
6