Electrical installation
Control terminals
Device variant with "Safe torque off" function
Supply via internal voltage source
If a freely assignable digital output (e.g. X5/A1) is assigned permanently to HIGH
ƒ
level, it serves as an internal voltage source. Every output has a maximum load
capacity of 50 mA.
– The relay K
voltage via a digital output.
– Two digital outputs must be connected in parallel and assigned permanently to
HIGH level in order to obtain the maximum wiring (relays K
X5/ST1).
For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you have to set a
ƒ
freely assignable analog output (e. g. X6/63) permanently to HIGH level.
+5 V
+
K
SR
X11 K31 K32 33 34
X5 28 E1 E2 E3 E4
S1
S2
IN1 IN2 IN3 IN4
Z1
Fig. 5−28
208
and two digital inputs (X5/28 and e.g. X5/E1) can be supplied with
SR
GND2
E5
39
A1
Wiring of digital and analog inputs/outputs with active "Safe torque off" function and internal
voltage source
S1
Deactivate pulse inhibit (1st disconnecting path)
S2
Enable controller (2nd disconnecting path)
Z1
Programmable logic controller (PLC)
The PLC monitors the ˜Safe torque off˜ function
X5/A4 Feedback via a digital output (e. g. DIGOUT4)
NO contact or NC contact
Load
Z
Minimum wiring required for operation
Terminal assignment in the Lenze setting: ^ 210
l
+24V
1
2
3
X3
4
5
6
A2 A3 A4 ST1ST2 59
X6
and X5/E1 ... X5/E5,
SR
GND1
GND1
242R
3.3nF
3
7
62 63
1
2
4
AOUT2
AIN1
AIN2
AOUT1
1
2
3
4
7
AOUTx
10k
10k
9300vec135
EDKVF9333V DE/EN/FR 7.2
7