Operating conditions
Ambient conditions
Climatic
Storage
Transport
Operation
EVF9321 ... EVF9326
EVF9327 ... EVF9333
Pollution
Site altitude
Mechanical
Vibration resistance
2
(9.81 m/s
Electrical
AC−mains connection
Max. mains voltage
range
Mains frequency
Power system TT, TN
Power system IT
Operation on public
supply systems
DC−mains connection
Max. mains voltage
range
Operating conditions
Motor connection
Length of the motor
cable
EDKVF9333V DE/EN/FR 7.2
IEC/EN 60721−3−1
IEC/EN 60721−3−2
IEC/EN 60721−3−3
IEC/EN 61800−5−1
Germanischer Lloyd
= 1 g)
5 ... 13.2 Hz
IEC/EN 60068−2−6
10 ... 57 Hz
EN 61000−3−2
l
Technical data
General data and operating conditions
1K3 (−25 ... +55 °C)
1K3 (−25 ... +40 °C)
2K3 (−25 ... +70 °C)
3K3 (0 ... +55 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.
3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.
Degree of pollution 2
< 4000 m amsl
> 1000 m amsl: reduce the rated output current by
5 %/ 1000 m.
Amplitude ±1 mm 13.2 ... 100 Hz:
acceleration resistant up to 0.7 g
Amplitude 0.075 mm 57 ... 150 Hz:
acceleration resistant up to 1 g
320 V − 0 % ... 528 V + 0 %
45 Hz − 0 % ... 65 Hz + 0 %
Operation permitted without restrictions with earthed
neutral.
Operation only permitted with the device variants V024 or
V100.
Operation permitted without restrictions with insulated
neutral.
Observe instructions on specific measures!
Limitation of harmonic currents
Total output at the mains
< 1 kW
> 1 kW
1)
The additional measures mentioned have the effect that solely the controllers
meet the requirements of EN 61000−3−2. The machine/system manufacturer is
responsible for the compliance with the requirements for the machine/system!
450 V − 0 % ... 740 V + 0 %
DC voltage must be symmetrical to PE.
The controller will be destroyed when +U
< 50 m
< 100 m
At rated mains voltage and a switching frequency of £ 8 kHz
without additional output filter.
For compliance with EMC regulations, the permissible cable
length might change.
< 6 months
> 6 months
> 2 years: form DC bus
capacitors
Compliance with the
1)
requirements
With mains choke.
Without additional measures.
or −U
are earthed.
G
G
shielded
unshielded
135
3