Mains Connection: Fuses And Cable Cross−Sections - Lenze 9300 vector Série Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5
Electrical installation
Standard devices in the power range 0.37 ... 11 kW
Mains connection: Fuses and cable cross−sections
Mains connection, DC supply
0
1
2
L1, L2, L3
+U , -U
G
Fig. 5−3
5.4.3
Mains connection: Fuses and cable cross−sections
Installation in accordance with EN 60204−1
Supply conditions
Range
Fuses
Cables
RCCB
Observe all national and regional regulations!
170
L1
L2
L3 +UG -UG
PE
0.5...0.6 Nm
4.4...5.3 lb-in
G
Mains connection, DC supply for drive controllers 0.37 ... 11 kW
0
Mains cable
1
Shield sheet
Securely clamp mains cable with the lugs
2
Mains and DC bus connection
L1, L2, L3: Connection of mains cable
+U
, −U
: Connection of DC−bus components or connection of the controller in the DC−bus
G
G
system (see system manual)
Cable cross−sections up to 4 mm
Cable cross−sections > 4 mm
Description
l
Utilisation category: only gG/gL or gRL
Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).
l
Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a
fault current monitoring unit (RCM) is used for protection in the case of direct or indirect
contact, only one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a
1−phase system
Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system
by using a transformer.
l
Earth−leakage circuit breakers must only be installed between mains supply and controller.
l
2
: Use wire end ferrules for flexible cables
2
: Use pin−end connectors
9300std033
EDKVF9333V DE/EN/FR 7.2