2 SPECIFICATION

2.1 Ordering codes of compact pH controllers 8205
8205 compact, 4-20 mA output, 15-30 VDC, 1 alarm relay
Pulse outputs
2 relays
2 transistors
2.2 Ordering codes of separate controllers 8205
Controller 8205, panel mounted, 4-20 mA output, 1 alarm relay
Pulse outputs
2 relays
2 transistors
Controller 8205, wall-mounted, 4-20 mA output, 1 alarm relay
Pulse outputs
2 relays
2 transistors
2 relays
2 transistors
pH sensor holders for pH controllers 8205 in separate versions: see instruction manual
"pH sensor holder 8200" (ordering code 428937)

2.3 Design and measuring principle

Design
pH controller 8205 compact
The pH-controller compactly combines a
pH-sensor and a controller with display in a
splash-proof enclosure.
The sensor component consists of a
replaceable combination pH-electrode,
screwed into the sensor housing with
screw-in threads. The measured signal is
conveyed to the controller via a coax plug.
The Pt1000 for automatic temperature
compensation is a standard feature in the
sensor housing.
The controller component converts the
measured signal, displays the actual value
and computes the command signals.
The output signals are provided via two
cable glands.
Gaskets
Electrode
FPM
Unitrode
FPM
Unitrode
Power supply
15-30 VDC
15-30 VDC
Power supply
15-30 VDC
15-30 VDC
115/230 VAC
115/230 VAC
PH CONTROLLER 8205
Electrical
connection
2 x M20x1,5 cable glands
2 x M20x1,5 cable glands
Electrical
connection
terminal strips
terminal strips
Electrical
connection
5 x M16x1,5 cable glands
5 x M16x1,5 cable glands
5 x M16x1,5 cable glands
5 x M16x1,5 cable glands
pH controller 8205, separate version
The pH transmission system combines a
pH sensor 8200, and a separate pH
controller 8205 with display.
The 8205 separate controller is available in
panel mounted version or in a wall-
mounted enclosure.
pH sensor 8200
The characteristics of electrodes are
described in the 8200 operating
manual.The Pt1000 for automatic
temperature compensation is available as
an option feature in pH sensor housings
type 8200.
E-3-
Ordering code
426430
426450
Ordering code
427939
427941
Ordering code
427946
427948
427951
427953