Programming
>
Volt Menu
Threshold detection starts from the loss of source
or source return sequence.
%
Controlled value (voltages)
100
LCD
Denomination / Definition
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.
96
ATyS
1
2
1
over voltage threshold
1
over voltage threshold hysteresis
1
under voltage threshold
1
under voltage threshold hysteresis
2
over voltage threshold
2
over voltage threshold hysteresis
2
under voltage threshold
2
under voltage threshold hysteresis
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
Over voltage threshold (oU)
Over voltage hysteresys
threshold (oUh)
Source available
t
Under voltage hysteresys
threshold (uUh)
Under voltage th reshold (uU)
Setting
range
From 102
to 120 %
From 101
to 119 %
From 80
to 98 %
From 81
to 99 %
From 102
to 120 %
From 101
to 119 %
From 80
to 98 %
From 81
to 99 %
SOCOMEC - Réf. : 532 211 F
Default
values
115 %
110 %
85 %
95 %
115 %
110 %
85 %
95 %