Frequency Menu - socomec ATyS 6m Notice D'utilisation

Masquer les pouces Voir aussi pour ATyS 6m:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Programming
>

Frequency Menu

Threshold detection starts from the loss of source
or source return sequence.
%
Controlled value (frequency)
100
LCD
Denomination / Definition
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Network
1
2
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.
SOCOMEC - Réf. : 532 211 F
1
2
1
over frequency threshold
1
over frequency threshold hysteresis
1
under frequency threshold
1
under frequency threshold hysteresis
2
over frequency threshold
2
over frequency threshold hysteresis
2
under frequency threshold
2
under frequency threshold hysteresis
Automatic Transfer Switch ATyS
OPERATION
Over frequency threshold (oU)
Over frequency hysteresys
threshold (oUh)
Source available
t
Under frequency hysteresys
threshold (uUh)
Under frequency threshold (uU)
Setting
range
From 101
to 120 %
From 100,5
to 119,5 %
From 80
to 99 %
From 80,5
to 99,5 %
From 101
to 120 %
From 100,5
to 119,5 %
From 80
to 99 %
From 80,5
to 99,5 %
Default
values
105 %
103 %
95 %
97 %
105 %
103 %
95 %
97 %
97