Installation; Dimensions - socomec ATyS 6m Notice D'utilisation

Masquer les pouces Voir aussi pour ATyS 6m:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Automatic Transfer Switch

INSTALLATION

ATyS 6m

Dimensions

125 to 630 A
W
10
X
Ø7
Ø9
Consider space required for handle operation
and cables connection.
1. Locking bracket with 3 padocks max
2. Maximum handle radius, operating angle 2 x 90°
3. Connection zone
4. Mounting spacer (accessory)
Rating
Overall
Terminal
(A)
dimensions
shrouds
A 3p. A 4p.
C
AC F 3p. F 4p.
125
304 340 244 235 286.5 322,5 151 154 184
160
304 340 244 235 286.5 322,5 151 154 184
250
345 395 244.5 280 328 378 153 195 245
400
345 395 244.5 280 328 378 153 195 245
630
394 459 320.5 400 377 437 221 244 304
68
ATyS
J
M
J1
U
T
T
T
11
F
A
1
W
U
Switch body
mounting
H
J 3p. J 4p. J 1 M 3p. M 4p.
34
120 150
34
120 150
35
160 210
35
160 210
34
210 270
3
4
10.5
Y
2
Z1
3
20
5. terminal shrouds (accessory)
6. Cut out
7. Removable handle
Switch
T
U
V
W
X 3p. X 4p.
36
20
25
9
36
20
25
9
50
25
30
11
50
35
35
11
65
45
50
13
Dimensions
Mounting orientation
Customer mounted accessories
Factory fitted accessories
48
Y
3
85
5
Z2
H
C
138
6
Connection terminals
Y
Z1
Z2
AA
28
22
3.5
38
134 135 115
28
22
3.5
38
134 135 115
33
33
3.5 39.5 134.5 160 130
33
33
3.5 39.5 134.5 170 140
42.5 37.5
5
53
190 260 220
SOCOMEC - Réf. : 532 211 F
7
BA
CA
10
10
15
15
20

Publicité

Table des Matières
loading

Table des Matières