Automatic Transfer Switch
CONNECTIONS
ATyS 6m
Voltage sensing and power supply kit
All sensing and power connections required to make
the product work are included.
Mount the kit before power cables
connection.
STANDARD CONFIGURATION
The kit is delivered from factory with the following confi-
guration:
• 3 phases network 400 / 230 Vac 4 wires or 230 Vac
3 wires
• bottom cables entry
• neutral conductor on the right (in case of 4 wires
configuration)
• source
1
connected to switch I.
The kit can be adapted to other configurations, but
then requires, connections and / or programming
modifications.
KIT INSTALLATION (FOR STANDARD 4 WIRES CONFIGURATION)
Load
Sources
≤
630 A
Bottom view
82
ATyS
≥
800 A
Bottom view
Power circuits
Control circuits
Voltage sensing and
power supply kit
Load
230 V
400 V
N
Source 1
Source 2
Be careful not to damage contacts during kit
mounting and power cables connections
(tighten cables carefully).
Specific strips
to fixe cables tray
Cables tray positionned
on the specific supports
SOCOMEC - Réf. : 532 211 F
1
2
FAST ON plug
connections