Control circuits
Denomination Terminals
(1)
Description
Power supply Power 101 Source
1
230 V~102
Power supply Power 201 Source
2
230 V~202
Sensing inputs N (103) Neutral
1
source
L3 (104) Phase 3
L2 (105) Phase 2
L1 (106) Phase 1
Sensing inputs L1 (203) Phase 1
2
source
L2 (204) Phase 2
L3 (205) Phase 3
N (206) Neutral
Commands
207
Commands inputs Common terminal
208
Standby source transfer control input (CTS)
209
Remote test on load input
210
DC power supply for 2I / 2O
Genset
73
Genset start / stop relay - 2 stable positions
start signal
(2)
74
Programmable state - factory setting = NO, close to start 5A AC1 / 250 V
Control
313
Control activation
(Impulse /
if closed with 317
contactor
314
Position
mode to
315
Position
refer to
316
Position 0 order if closed with 317
programming) 317
Specific voltage supply
Common control terminals 313 to 316
Remote interface RJ
ATyS D10 or D20 connection
conection
Position
13
Common I - 0 - II
auxiliary
14
AC position I NO
contacts
24
AC position II NO
34
AC position 0 NO
Auxiliary
43
Auto / manu selector position
contacts
44
Closed in automatic position
/ AUT &
53
Padlocked information
Padlock
54
Closed if padlock is in place
Fault
63
Relay closed when product is faulty
relay
64
(if product is powered)
Second
81
Common AC position I
auxiliary
82
AC position I NC
contact
84
AC position I NO
(option)
91
Common AC position II
92
AC position II NC
94
AC position II NO
Option
0
Connection RS485
Communication -
+
Option
I13 +
Input
2 Inputs /
I14 -
Function according to programming
2 Outputs
I23 +
Input
I24 -
Function according to programming
O13
Output Relay
O14
Function according to programming
O23
Output Relay
O24
Function according to programming
Current
R1
Current transformer I1
transformer
R2
S1
Current transformer I2
S2
T1
Current transformer I3
T2
Voltage and frequency sensing precision: 1 %
(1) Terminal numbers can differ depending on voltage sensing and power supply kit configuration.
(2) Refer to programming, Setup, to modify relay state.
(3) It is recommended to power 2I / 2O modules from terminals 207-210 (refer to connection diagram).
SOCOMEC - Réf. : 532 211 F
1
2
2
order if closed with 317
1
order if closed with 317
Automatic Transfer Switch ATyS
CONNECTIONS
Characteristics
220 to 240 Vac ±20 %
500 Vac (phase-phase)
maximum
288 Vac (phase-neutral)
maximum
500 Vac (phase-phase)
maximum
288 Vac (phase-neutral)
maximum
Do not connect to any
power supply
Dry contact
Do not connect to any
power supply
Maximum distance 3 m
5A AC1 / 250 V
5A AC1 / 250 V
5A AC1 / 250 V
5A AC1 / 250 V
To power from 10 to 30 Vdc
(3)
(3)
To power from 10 to 30 Vdc
5A AC1 / 250 V
CT input 5 A
CT input 5 A
CT input 5 A
Recommended
section
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
4 mm
2
1.5 mm
2
RJ45 8 / 8
1.5 mm
2
1.5 mm
2
2
1.5 mm
2
1.5 mm
1.5 mm
2
2
1.5 mm
2
1.5 mm
2
1,5 mm
1,5 mm
2
1,5 mm
2
81