Programming
CARACTÉRISTIQUES DES VARIABLES
>
Menu Setup
1
LCD
Denomination
Type of
network*
1
2
Network
nominal voltage
1
2
Network
nominal
1
2
frequency
CTs ratio
1
2
Source 1 -
Switch I or II
1
2
configuration
Genset start
signal state
1
2
Network priority
selection
1
2
Manual
Retransfer
1
2
Type of control
logic selection
1
2
Number of
permutation
1
2
counter Reset
Programming
code
1
2
modification
* refer to annexes
SOCOMEC - Réf. : 532 211 F
2
Definition
Number of active conductors of controlled
network (refer to annexes)
Phase-Neutral voltage for 1BL & 41NBL
Phase-Phase voltage for others
Network nominal frequency
Current transformers ratio (Primary/Secondary) from 50 / 5 to
1
Source
(controlled and displayed) linked to
switch I or II (depending on cabling)
Normally opened or closed
Keypad selection (1 or 2)
Also possible via external contact
Using option
Activation of the feature
Impulse or contactor
Allows source
1
sequences counter reset
Possible to change the programming code
Automatic Transfer Switch ATyS
-> source
2
automatic
OPERATION
Setting
Default
range
values
4NBL, 2NBL,
4NBL
2BL, 1BL,
3NBL, 41NBL,
42NBL
from 110 V
400 Vac
to 480 V
50 or 60 Hz
50 Hz
500 / 5
1600 / 5
I or II
I
NO or NC
NO
1
2
1
or
Yes or No
No
IMP or CON
IMP
Yes or No
No
From 0001
1000
to 9999
95