Automatic Transfer Switch
OPTIONS
ATyS 6m
Communication module
Decimal
Hexa.
address
address
553
229
554
22A
555
22B
556
22C
557
22D
558
22E
559
22F
>
Example
Nominal voltage (233 V) configuration on ATyS n° 5.
Slave
Function
Hex
05
10
Déc.
16
ATyS answer:
Slave
Hex
05
116
ATyS
Number
of words
1
1
1
1
1
1
1
High-order
Low-order
address
address
02
06
Value
Function
high-order
10
02
Communication module
Text
Output Ou2
0 = / - 1 = S1A
2 = S2A - 3 = LS
Input In3
0 = / - 1 = Ft1 - 2 = Ft2
3 = Pri - 4 = S2A - 5 = MtF
Input In3 state
0 = NO - 1 = NC
Input In4
0 = / - 1 = Ft1 - 2 = Ft2
3 = Pri - 4 = S2A - 5 = MtF
Input In4 state
0 = NO - 1 = NC
Output Ou3
0 = / - 1 = S1A
2 = S2A - 3 = LS
Output Ou4
0 = / - 1 = S1A
2 = S2A - 3 = LS
First word
Number
Word n°
of bytes
high order
00
01
02
Value
low-order
06
00
Unit
First word
CRC 16
low order
00
E9
76B8
233
Word n°
CRC 16
01
E1F4
SOCOMEC - Réf. : 532 211 F