CONNECTIONS
ATyS 6m

Control circuits

EXAMPLE: 400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
R1 R2 S1 S2 T1 T2
L1
L2
2
2
L3
N
-
I
14
C
O
M
O
0
-
+
24
Verify power supply terminals 101-102 and
201-202: 230 Vac nominal.
3 current transformers connections
mendatory.
Short circuits CTs secondary before disconnecting connector.
80
ATyS
F2
I
13 14 24
+
I
I
I
I
I
I
I
13
24
23
14
13
24
23
O
O
O
O
O
O
O
23
14
13
24
23
14
13
LOAD
* Current transformer In / 5 A
*
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
I1
I2
I3
4
3
2
1
RJ45 8/8 link
II
0
AUT
34 43
44 53 54
81 82 84
Maximum control cables length = 10 m. In
case of longer distance, insert control relays.
Remote interfaces maximum connection
cable (RJ45) = 3 m.
Power circuits
Control circuits
Voltage sensing and
power supply kit
L1
L2
1
1
L3
N
F1
F1, F2
Fuse protection
230 Vac 5 A
Inhibition
2
1
0
Remote Interface
I
II
ATyS D10 or D20
91 92 94
SOCOMEC - Réf. : 532 211 F