TECHNICAL CHARACTERISTICS

SOCOMEC - Ref. : 875 510A
CASE
Dimensions:
or 96 x 96 x 80 mm with all optional modules (DIN 43700)
Connection:
(voltage and others) and 6 mm
IP index:
Weight:
DISPLAY
Type:
MEASUREMENTS
Three-phase (3 or 4 wires), two-phase (1 wire) and single-phase networks
VOLTAGE (TRMS)
Direct measurement:
Measurement via PT:
• Primary:
• Secondary:
Display and resolution
Permanent overload:
Update period:
CURRENT (TRMS)
Via CT with:
• Primary:
• Secondary:
Input consumption:
Display:
permanent overload:
intermittent overload:
Update period:
Maximum ratio KI x KU:
POWER
Per phase:
Total:
Update period:
FREQUENCY
from 45,0 to 65,0 Hz
Update period:
MEASUREMENT ACCURACY
Current:
Voltage:
Power:
Power factor:
Frequency:
Active energy metering:
+/- 1% from 0.02 to 1,2 In with PF = 0.5 L or 0.8 C (class 1 IEC 1036)
Reactive energy metering:
+/- 2% from 0.1 to 1,2 In with sinϕ = 0.5 L or C (class 1 IEC 1268)
via 2.5 mm
2
disconnectable terminals
2
fixed terminals (current)
IP54 (front panel) and IP20 (case)
High luminosity self adjusting LCD display
from 0 to 700 V AC (phase/phase)
from 0 to 404 V AC (phase/neutral)
60, 100, 110, 173 and 190 V AC
from 0 to 11 kA (1.1 times the primary value)
0 to 1660 MW/Mvar/MVA
0 to 8000 MW/Mvar/MVA
0.5 % from 10 to 110 % / In
0.5 % from 140 to 760 V AC
1 % of full scale (-90° à + 90°)
1 % for 0.5 < FP < 1
0.1 Hz from 45 to 65 Hz
96 x 96 x 60 mm
400 gr.
up to 400 kV
from 0 to 400.0 kV
760 V AC
1 second
up to 10000 A
1 or 5 A
0.1 VA
6 A
10 In / 1 second
1 second
2 000 000
1 second
1 second
57