PRELIMINARY OPERATIONS
NB:
For personnel and product safety
please read the contents of these
operating instructions carefully before
connecting.
GENERAL INFORMATION
NB:
Meters can be programmed to reset to
zero (programme access via access
code).
Only one module can be fitted per
Diris Ap.
32
32
Check the following points as soon
as you receive the Diris Ap package:
• the packing is in good condition,
• the product has not been damaged
during transit,
• the product reference number
conforms to your order,
FUNCTIONS
The Diris Ap is an instrument for mea-
suring and metering electrical values
for single, two and three-phase LV/HV
electrical networks. From the front
panel (6 keys and LCD displays) you
can programme and display all the
parameters and use the functions
provided to carry out the following:
TRMS (TRUE ROOT MEAN SQUARED) MEASUREMENT:
• instantaneous, average and maxi-
mum current over a programmable
integration time (5 to 60 min.),
• phase to neutral and phase to pha-
se voltage,
• frequency,
• instantaneous, average and maxi-
mum active power P on 4 display
quadrants (L/C/+/-) over a program-
mable integration time (5 to 60 min.),
• instantaneous, average and maxi-
mum reactive power Q on 4 display
quadrants (L/C/+/-) over a program-
mable integration time (5 to 60 min.),
HOUR METERING
Metering in 1/100th of an hour for
operating time, with reset to zero.
OPTIONS
Options are integrated in easy click-
on modules and can be added by the
user before during or after installa-
tion. Each module can be placed in
any of the four positions. Available
options are as follows:
• Energy metering
Active (0 to 99 999 999 kWh) and
reactive energy metering on 4 qua-
drants. Two programmable pulse
outputs can be used for active,
• the package contains the product
fitted with a fixed current terminal
as well as a pull-out terminal block
for the auxiliary supply and voltage
inputs,
• operating instructions.
• measure electrical values on 4 qua-
drants
• hours run meter
Optionally, the product can be fitted
with an energy metering and commu-
nication function.
• instantaneous, average and maxi-
mum apparent power S over a pro-
grammable integration time (5 to
60 min.),
• instantaneous and maximum power
factor PF with L (inductive) and C
(capacitive) indications.
reactive or apparent energy mete-
ring, with a programmable value
(0,1, 1, 10, 100 kWh, kvarh or kVAh
and 1 or 10 MWh, Mvarh and MVAh)
and duration (100 ms to 900 ms).
• Communication
An RS485 serial link (2 or 3 wires)
with JBUS/MODBUS protocol for
use with a PC or PLC.
SOCOMEC - Ref. : 875 510A
SOCOMEC - Ref. : 875 510A