Press once
Press once
10
PROGRAMMING N° 1 PULSE OUTPUT TYPE (OUt 1 TYPE)
NB: The energy type default setting is active energy (EA). If you want this value, press
output value programming (OUt 1 VAL). If not, proceed as follows:
KEYS
INSTRUCTION
Press once
Press once
Press once
Press once
11
PROGRAMMING N° 1 PULSE OUTPUT VALUE (OUt 1 VAL)
NB: The value default setting is 10 (VAL 10). If you want this value, press
tion programming (OUt 1 DUR). If not, proceed as follows:
KEYS
INSTRUCTION
Press once
SOCOMEC - Ref. : 875 510A
Yes to set to zero
Confirm parameter.
Press on
programming.
DISPLAY
COMMENT
to display flashing EA
Press again for:
ES, EA - , ER - and EA
or
Press again for:
EA-, ES, ER and EA
Confirm type.
Press to pass
programming (VAL)
. You will pass to N° 1 pulse output dura-
DISPLAY
COMMENT
to display flashing 10 kWh, kvarh, kVAh
to pass to type OUt1
(OPTION)
. You will pass to N° 1 pulse
to value
(OPTION)
43