Press once
3
PROGRAMMING THE CURRENT TRANSFORMER RATIO (Ct)
NB: The default Ct setting is 500/5. If you want this setting, press
If not, proceed as follows:
KEYS
INSTRUCTION
Press once
Press
to decrement or
Press
once to confirm value
Press
once to pass to Vt programming
NB: the first 5 digits correspond to the transformer primary value (1 to 10000), and the last digit to the transformer
secondary value (1 or 5 A).
Example : Programming 1500/5 once in the Ct menu.
KEYS
INSTRUCTION
Press twice
Press once
Press once
SOCOMEC - Ref. : 875 510A
to increment selected digit value
Confirm type.
Press on
programming.
. You will pass to the voltage transformer line (Vt).
DISPLAY
COMMENT
Press as many times as necessary to
move to the right, or press
to the left.
DISPLAY
COMMENT
To display flashing the 2
To increment the 2
To confirm the ratio.
Press on
programming.
to pass to Ct
to move
nd
digit
digit
nd
to pass to Vt
39