Technical Characteristics; Operating Conditions - socomec DIRIS A40 Notice D'utilisation

Masquer les pouces Voir aussi pour DIRIS A40:
Table des Matières

Publicité

GB
CASE
Dimensions:
Connection:
IP index:
Weight:
DISPLAY
Type :
MEASUREMENTS
Three-phase (3 or 4 wires), two-phase (2 wire) and single-phase networks
VOLTAGE (TRMS)
Direct measurement:
Measurement via PT:
Display and resolution
Permanent overload:
Update period:
CURRENT (TRMS)
Via CT with:
Minimum measuring current
Input consumption:
Display:
permanent overload:
intermittent overload:
Update period:
Maximum ratio KI x KU:
POWER
Total:
Update period:
FREQUENCY
Update period:
AUXILIARY SUPPLY IEC / CE
110 to 400 V AC 50/60 Hz
120 to 350 V DC
12 to 48 V DC
Consumption:

OPERATING CONDITIONS

Operating temperature:
Storage temperature:
Relative humidity:
96 x 96 x 60 mm
or 96 x 96 x 80 mm with all optional modules (DIN 43700)
via 2.5 mm
disconnectable terminals
2
(voltage and others) and 6 mm
IP52 (front panel) and IP30 (case)
400 gr.
Backlit LCD display
from 18 to 700 V AC (phase/phase)
from 11 to 404 V AC (phase/neutral)
• Primary:
up to 500 kV
• Secondary:
60, 100, 110, 115, 120, 173 and 190 V AC
from 0 to 500.0 kV
760 V AC
1 second
• Primary:
up to 9995 A
• Secondary:
1 or 5 A
10 mA
< 0.3 VA
from 0 to 11 kA (1.1 times the primary value)
10 A
10 In / 1 second
1 second
10 000 000
0 to 8000 MW/Mvar/MVA
1 second
from 45,0 to 65,0 Hz
1 second
± 10 %
± 20 %
-6 % / + 20 %
< 10 VA
-10° to + 55°C (14° to 131°F)
-20° to + 85°C (-4° to 158°F)
95 %
DIRIS A40 / A41

TECHNICAL CHARACTERISTICS

2
fixed terminals (current)
DIRIS A40/A41 - Ref.: 535 747 A
53

Hide quick links:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Diris a41

Table des Matières