COMMUNICATION (OPTION)
Slave address
NB:
When selecting slave address 0, a
message is sent to all the instruments
present on the network (only for func-
tions 6 and 16).
SOCOMEC - Ref. : 875 510A
The JBUS/MODBUS
Diris Ap involves a dialogue using a
master-slave hierarchical structure.
There are two possible dialogues:
• the master communicates with a
slave (Diris Ap) and waits for its
reply
• the master communicates with all
the slaves (Diris Ap) without waiting
for their reply.
The standard communications frame
consists of:
Function code
Address
According to the JBUS/MODBUS
protocol, transmission time must be
less than 3 silences, i.e. the emission
time of 3 characters so that the mes-
sage is processed by the Diris
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
TABLE OF VALUES WITH ALLOCATED CURRENT AND VOLTAGE WINDING RATIOS
Decimal
Hexa.
address address of words
768
300
770
302
772
304
774
306
776
308
778
30A
780
30C
782
30E
784
310
786
312
788
314
790
316
792
318
794
31A
796
31C
798
31E
800
320
802
322
804
324
806
326
808
328
810
32A
812
32C
814
32E
816
330
818
332
©
used by the
The mode of communication is the
RTU (Remote Terminal Unit) using
hexadecimal characters of at least 8
bits.
Data
©
To correctly use information, the fol-
lowing functions are important:
3 : to read n words (maximum
©
.
6 : to write one word.
8 : to diagnose exchanges bet-
16 : to write n words (maximum
Number
Text
2
phase 1 current
2
phase 2 current
2
phase 3 current
2
Neutral current
2
phase to phase voltage U12
2
phase to phase voltage U23
2
phase to phase voltage U31
2
phase to neutral voltage phase 1
2
phase to neutral voltage phase 2
2
phase to neutral voltage phase 3
2
Frequency
∑ Active power +/-
2
∑ Reactive power +/-
2
∑ Apparent power +/-
2
∑ Power factor
2
-: capacitive et +: inductive
2
Active power phase 1 +/-
2
Active power phase 2 +/-
2
Active power phase 3 +/-
2
Reactive power phase 1 +/-
2
Reactive power phase 2 +/-
2
Reactive power phase 3 +/-
2
Apparent power phase 1
2
Apparent power phase 2
2
Apparent power phase 3
2
Power factor phase 1
-: capacitive et +: inductive
2
Power factor phase 2
-: capacitive et +: inductive
CRC 16
128).
ween the master and the slave
via meters 1, 3, 4, 5 and 6.
128).
Unit
mA
mA
mA
mA
V/100
V/100
V/100
V/100
V/100
V/100
Hz/100
kW/100
kvar/100
kVA/100
0,001
kW/100
kW/100
kW/100
kvar/100
kvar/100
kvar/100
kVA/100
kVA/100
kVA/100
0,001
0,001
51