To reset several parameters to zero,
add the corresponding figure indica-
ted in the "text" column.
Example: reset Max P+ and kvarh + to
zero: 2 = 100 = 102 (Hex)
Slave
Function
05
NB:
Diris Ap will not
reply to this com-
mand.
56
RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6)
Decimal Hexad.
address address
1024
Zone size: 1 word or 1 hexadecimal
Example:
To reset all values for DIRIS number 5
to zero, the following frame should be
sent:
High-order
address
06
04
Diris Ap reply: identical to the message
sent.
SAVED COMMAND (RESET)
The following command should be
done to save programming parame-
ters changes for DIRIS number 5.
Slave
Function
05
06
N° of
words
400
1
all parameters:1000
Low-order
High-order
address
word n°
00
10
High-order
Low-order
address
address
06
00
Text
Hex
reset to zero for:
Max3I:1
MaxP+:2
MaxP-:4
MaxQ+:8
MaxQ-:10
MaxS:20
Hour meter:40
kWh+:80
kvarh+:100
kVA:200
kWh-:400
kvarh-:800
Low-order
word n°
00
Values
0000
SOCOMEC - Ref. : 875 510A
Unit
/
CRC 16
84BE
CRC 16
88C6