6.4.3 Connection of the alarm inputs
and relays
CAUTION! TNV-1 installation type. The
installation is type TNV-1, do not connect it
to SELV circuits.
CAUTION! In order to reduce the risk of fire,
only use UL Listed or CSA certified cables
with sections greater than or equal to
0.14mm² (26AWG).

Standard version

Fig. 14
Relay contact connection.
Fig. 15
Alarms connection.
16
O1 C1 O2 C2
V
V
ALARMS
AL2
AL4
AL1
AL3
Version with LED illuminators
CONNECTION OF THE ALARM INPUTS, OF THE TWILIGHT SWITCH
AND OF THE RELAYS
AL1, AL2, AL3,
Self-powered alarm inputs referring to the
AL4 e ALARMS
ALARMS common terminal
O1-C1 e O2-C2 Clean output contacts, can be activated by alarm
or by user control
Tab. 4
6.5 Connection of the Ethernet
cable
This chapter applies to IP models of the
product.
Connect the ethernet cable to the relative connector
(Ethernet, 6.3 Connector board description, page 13).
Fig. 16

6.6 Video cable connection

This chapter applies to analog models of
the product.
Connect the screen and central cable
respectively to the GND and VIDEO
terminals. The terminals accept cables with
sections between 0.5mm² (20 AWG) and
0.08mm² (28AWG).
The analog signal video cable must be connected to
the signal cable terminal (CN4, 6.3 Connector board
description, page 13).
Fig. 17
Ethernet
MNVCUPKT_1838_EN